Advantech EKI-1224 / CI / I

SPHINX in Europa
DE
  • AT
  • BE
  • DK
  • FR
  • DE
  • IE
  • IT
  • NL
  • ES
  • SE
  • CH
  • UK
Produktgruppen > Gateways > Advantech EKI-1224 / CI / I

Advantech EKI-1224 / CI / I

Industrial 4-port Modbus Gateway

Advantech EKI-1224 / CI / I
7971_34679.png
7971_34680.jpg
7971_34699.jpg
  • EigenschaftenEigenschaften
  • BeschreibungBeschreibung
  • Weitere InformationenWeitere Informationen
  • PDFPDF
  • Provides 2 x 10/100 Mbps Ethernet ports for LAN redundancy
  • Integration of Modbus TCP and Modbus RTU/ASCII networks
  • Supports up to 921.6 kbps, and any baud rate setting
  • Support up to 16 connections on each serial port under Modbus client mode and 32 sessions under Modbus server mode.
  • Mounts on DIN-rail, wall or panel
  • Software selectable RS-232/422/485 communication
  • Automatic RS-485 data flow control
  • "I" models support a wide operating temperature
  • "CI" models support isolation and a wide operating temperature
The EKI-1200 series Modbus gateways are bi-directional gateways for integrating new and existing Modbus/RTU and Modbus/ASCII serial devices
to newer TCP/IP networked-based devices.
The EKI-1224 feature two independent Ethernet ports and MAC addresses to provide a redundant networking mechanism.
ProdGrafik

Specifications

Ethernet Communications
Compatibility IEEE 802.3, IEEE 802.3u
Speed 10/100 Mbps
No. of Ports 2
Port Connector 8-pin RJ45
Protection Built-in 2.25 k VDC magnetic isolation
Serial Communications
Port Type RS-232/422/485-2w/485-4w, software selectable
(EKI-1224CI-CE supports RS-422/485 only)
No. of Ports EKI-1221: 1
EKI-1222: 2
EKI-1224: 4
Port Connector DB9 male
EKI-1221CI-DE; EKI-1222CI-DE also provide Terminal Block
Data Bits 5, 6, 7, 8
Stop Bits 1, 1.5, 2
Parity None, Odd, Even, Space, Mark
Flow Control XON/XOFF, RTS/CTS
Baud Rate 50 bps ~ 921.6 kbps, any baud rate setting
Serial Signals [CE Version]
RS-232: TxD, RxD, CTS, RTS, DCD, RI, GND, DTR, DSR
RS-422: TxD+, TxD-, RxD+, RxD-, GND
RS-485 2-wire: Data+, Data-, GND
[DE Version]
DB9:
RS-232 isolation: TxD, RxD, CTS, RTS, GND
RS-232: TxD, RxD, CTS, RTS, DCD, RI, GND, DTR, DSR
Terminal Block ( From top to bottom):
RS-422: GND, RxD-, RxD+, TxD+, TxDRS-
485 2-wire: GND, NC, NC, TxD+, TxDRS-
485 4-wire: GND, RxD-, RxD+, TxD+, TxD-
Protection 15 KV ESD for all signals
Software
OS Support Windows XP/7/8.1/10, Windows Server
2003/2008/2012/2016/2019, and Linux
Utility Software Modbus RTU Master/Slave mode
Modbus ASCII Master/Slave mode
Configuration Windows Utility, Telnet Console, Web Browser
Protocols ICMP, IP, TCP, UDP, BOOTP, DHCP, Auto IP, HTTP, DNS, SMTP, ARP, NTP
General
LED Indicators System: Power, System Status
LAN: Speed, Link/Active
Serial: Tx, Rx
Reboot Trigger Built-in WDT (watchdog timer)
Mechanics
Dimensions (W x H x D) EKI-1221/I-CE; EKI-1221CI-DE; EKI-1222/I-CE; EKI-1222CI-DE:
30 x 140 x 95 mm (1.18" x 5.51" x 3.74")
EKI-1224/CI/I-CE:
42 x 140 x 95 mm (1.65" x 5.51" x 3.74")
Enclosure Metal with solid mounting hardware
Mounting DIN-rail, Wall
Weight EKI-1221: 0.472 Kg
EKI-1222: 0.48 Kg
EKI-1224: 0.555 Kg
IP Rating IP30
Power Requirements
Power Input 12 ~ 48 VDC, redundant dual inputs
Power Connector Terminal block
Power Consumption EKI-1221: 3.2 W
EKI-1222: 3.2 W
EKI-1224: 4.1 W
Environment
Operating Temperature EKI-1221/EKI-1222/EKI-1224:
-10 ~ 60 °C (14 ~ 140 °F)
'CI & I' models:
-40 ~ 80 °C (-40 ~ 176 °F)
Storage Temperature -40 ~ 85 °C (-40 ~ 185 °F)
Operating Humidity 10 ~ 95% RH
Regulatory Approvals
EMC CE, FCC Part 15 Subpart B (Class A)
Hazardous location UL/cUL (Class I, Division 2, Groups A, B, C and D), ATEX (Zone 2 Ex nA nC IIC T4 Gc)    
Port to Port Isolation ('CI' models)
Serial to Ethernet 2 kV
Serial to Power 2 kV
Ethernet to Power 1.5 kV




Ordering Information

EKI-1221-CE 1-port RS-232/422/485 Modbus Gateway
EKI-1222-CE 2-port RS-232/422/485 Modbus Gateway
EKI-1224-CE 4-port RS-232/422/485 Modbus Gateway
EKI-1221I-CE 1-port RS-232/422/485 Modbus Gateway with Wide Operating Temperature
EKI-1222I-CE 2-port RS-232/422/485 Modbus Gateway with Wide Operating Temperature
EKI-1224I-CE 4-port RS-232/422/485 Modbus Gateway with Wide Operating Temperature
EKI-1221CI-DE 1-port RS-232/422/485-2w/485-4w Modbus Gateway with Wide operation temperature and isolation
EKI-1222CI-DE 2-port RS-232/422/485-2w/485-4w Modbus Gateway with Wide operation temperature and isolation     
EKI-1224CI-CE      4-port RS-422/485 Modbus Gateway with Wide Operation Temperature and Isolation
OPT1-DB9 D-Sub9 to Terminal Converter