LEGRAND MEGALINE
Single-phase modular UPS systems from 1.25 to 10 kVA
![LEGRAND MEGALINE](https://www.sphinxcomputer.de/produktdb/images/products/5960_18694.png)
![5960_18694.png](https://www.sphinxcomputer.de/produktdb/images/products/5960_18694.png)
![5960_18695.jpg](https://www.sphinxcomputer.de/produktdb/images/products/5960_18695.jpg)
![5960_18696.jpg](https://www.sphinxcomputer.de/produktdb/images/products/5960_18696.jpg)
![5960_18697.jpg](https://www.sphinxcomputer.de/produktdb/images/products/5960_18697.jpg)
![5960_18698.jpg](https://www.sphinxcomputer.de/produktdb/images/products/5960_18698.jpg)
- Single-phase modular UPS systems
- Power from 1250 to 10000 VA
- VFI-111 on-line double conversion
- Adaptable, expandable and redundant solutions
- Easy and fast management and maintenance
- Low environmental impact (high efficiency and reduced footprint)
- UPS system in a single or double cabinet depending on the power
MEGALINE UPS is a single phase uninterruptible power supply with high frequency PWM technology, On Line Double Conversion type, modular architecture, with the possibility of N+X redundant configuration.
It delivers a rated power from 1250 to 10000VA, equipped with valve-regulated hermetic-type accumulator batteries, contained inside the UPS in a specific compartment or in one or more external cabinets.
Functions
- Wide voltage range and input frequency
- Operating frequency from 50 to 60 Hz with auto-recognition
- Frequency conversion 50 in – 60 out or vice versa
- Extension of the input frequency range for operation with power-supply units
- Operation in eco mode (energy-saving)
- Possibility to set on line mode with a minimum load rate
- Adjustable output voltage with 1V intervals from front panel
- Low level of noise
- Measures internal and external temperature
- Controls the ventilation in relation to the temperature and the load
- Designed for remote emergency switch-off
![ProdGrafik](https://www.sphinxcomputer.de/produktdb/images/products/5960_18698.jpg)
Characteristics
General characteristics Single cabinet | 3 103 42 3 103 46 3 103 50 | 3 103 43 3 103 47 3 103 52 | 3 103 44 3 103 48 3 103 54 | 3 103 45 3 103 49 3 103 56 |
Nominal power (VA) | 1250 | 2500 | 3750 | 5000 |
Active power (W) | 875 | 1750 | 2625 | 3500 |
Max. expansion (VA) | 5000 | |||
Max. expansion (W) | 3500 | |||
Technology | On-line double conversion VFI-SS-111 | |||
Architecture | Modular, expandable, N+X redundant with 1250 VA power cards,contained in a single cabinet | |||
Input characteristics | ||||
Nominal input voltage | 230 V | |||
Input voltage range | 184 V to 264 V at 100% load | |||
Minimum operating voltage | 100 V at 50% load | |||
THD of input current | < 3% | |||
Input power factor | > 0.99 at 20% load | |||
Input frequency | 50 Hz/60 Hz ± 2% autosensing | |||
Output characteristics | ||||
Output voltage | 230 V ± 1% | |||
Output frequency | 50 Hz/60 Hz synchronised | |||
THD of output voltage | < 1% with non-linear load | |||
Waveform | Sinusoidal | |||
Peak factor | 1:3 | |||
Efficiency | up to 92% | |||
Overload capacity | 300% for 1 s – 200% for 5 s – 150% for 30 s | |||
Backup time | ||||
Backup time (min) | 13 | |||
Extension of backup time | Yes | |||
Equipment | ||||
Bypass | Automatic, internally synchronised, static and electromechanical (for overloads and operating problems) | |||
Signalling and alarms | Wide screen with 4 alphanumeric lines, multi-coloured status indicator, audible signalling | |||
Communication ports | 1 RS 232 port, 2 logic level ports | |||
Communicator UPS software | Can be downloaded free of charge (after requesting an activation code) | |||
Protection | Electronic devices for protection against overloads, short-circuits and excessive battery discharge. Operation stops at end of backup time. Inrush current limiter on start-up. Sensor for correct neutral switching. Back-feed protection (electrical safety insulation of the input plug during battery-based operation). EPO (emergency power off) contact. | |||
I/O mains connection | German standard/terminal connector with universal multi-socket outlet (Italian/German standard) | |||
Mechanical characteristics | ||||
Net weight (kg) | 23,5 | 34 | 43 | 53 |
Dimensions W x H x D (mm) | 475 x 270 x 570 | |||
Installed power cards | 1 | 2 | 3 | 4 |
Free power expansion slots | 3 | 2 | 1 | - |
Installed battery kits | 1 | 2 | 3 | 4 |
Free backup time extension slots | 3 | 2 | 1 | - |
Ambient conditions | ||||
Ambient operating temperature (°C) | 0 to 40°C | |||
Protection index | IP 21 | |||
Relative humidity (%) | 20 to 80% | |||
Noise at 1 m (dBA) | < 40 | |||
Certifications | ||||
Reference product standards | EN 62040-1, EN 62040-2, EN 62040-3 |
General characteristics Double cabinet | 3 103 60 + 3 107 78 | 3 103 63 + 3 107 79 | 3 103 66 + 3 107 80 | 3 103 69 + 3 107 81 | 3 103 72 + 3 107 82 |
Nominal power (VA) | 5000 | 6250 | 7500 | 8750 | 10000 |
Active power (W) | 3500 | 4375 | 5250 | 6125 | 7000 |
Max. expansion (VA) | 10000 | ||||
Max. expansion (W) | 7000 | ||||
Technology | On-line double conversion VFI-SS-111 | ||||
Architecture | Modular, expandable, N+X redundant with 1250 VA power cards,contained in a single cabinet | ||||
Input characteristics | |||||
Nominal input voltage | 230 V | ||||
Input voltage range | 184 V to 264 V at 100% load | ||||
Minimum operating voltage | 100 V at 50% load | ||||
THD of input current | < 3% | ||||
Input power factor | > 0.99 at 20% load | ||||
Input frequency | 50 Hz/60 Hz ± 2% autosensing | ||||
Output characteristics | |||||
Output voltage | 230 V ± 1% | ||||
Output frequency | 50 Hz/60 Hz synchronised | ||||
THD of output voltage | < 1% with non-linear load | ||||
Waveform | Sinusoidal | ||||
Peak factor | 1:3 | ||||
Efficiency | up to 92% | ||||
Overload capacity | 300% for 1 s – 200% for 5 s – 150% for 30 s | ||||
Backup time | |||||
Backup time (min) | 13 | ||||
Extension of backup time | Yes | ||||
Equipment | |||||
Bypass | Automatic, internally synchronised, static and electromechanical (for overloads and operating problems) | ||||
Signalling and alarms | Wide screen with 4 alphanumeric lines, multi-coloured status indicator, audible signalling | ||||
Communication ports | 1 RS 232 port, 2 logic level ports | ||||
Communicator UPS software | Can be downloaded free of charge (after requesting an activation code) | ||||
Protection | Electronic devices for protection against overloads, short-circuits and excessive battery discharge. Operation stops at end of backup time. Inrush current limiter on start-up. Sensor for correct neutral switching. Back-feed protection (electrical safety insulation of the input plug during battery-based operation). EPO (emergency power off) contact. | ||||
I/O mains connection | German standard/terminal connector with universal multi-socket outlet (Italian/German standard) | ||||
Mechanical characteristics | |||||
Net weight (kg) | 24 + 50 | 26,5+57,5 | 29 + 65 | 31,5+72,5 | 34 + 80 |
Dimensions W x H x D (mm) | 2 x 475 x 270 x 570 | ||||
Installed power cards | 4 | 5 | 6 | 7 | 8 |
Free power expansion slots | 4 | 3 | 2 | 60 | - |
Installed battery kits | 4 | 5 | 6 | 7 | 8 |
Free backup time extension slots | 6 | 5 | 4 | 3 | 2 |
Ambient conditions | |||||
Ambient operating temperature (°C) | 0 to 40°C | ||||
Protection index | IP 21 | ||||
Relative humidity (%) | 20 to 80% | ||||
Noise at 1 m (dBA) | < 40 | ||||
Certifications | |||||
Reference product standards | EN 62040-1, EN 62040-2, EN 62040-3 |
ORDERING INFORMATIONS
Avaibles Modules Single cabinet (German standard) | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 50 | 1250 | 875 | 13 | 1 | 23,5 |
3 103 52 | 2500 | 1750 | 13 | 1 | 34 |
3 103 54 | 3750 | 2625 | 13 | 1 | 43 |
3 103 56 | 5000 | 3500 | 13 | 1 | 53 |
Avaibles Modules Double cabinet | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 60 + 3 107 78 | 5000 | 3500 | 13 | 2 | 24+50 |
3 103 63 + 3 107 79 | 6250 | 4375 | 13 | 2 | 27+58 |
3 103 66 + 3 107 80 | 7500 | 5250 | 13 | 2 | 29+65 |
3 103 69 + 3 107 81 | 8750 | 6125 | 13 | 2 | 32+73 |
3 103 72 + 3 107 82 | 10000 | 7000 | 13 | 2 | 34+80 |
Avaibles Modules Single cabinet (French standard) | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 42 | 1250 | 875 | 13 | 1 | 23.5 |
3 103 43 | 2500 | 1750 | 13 | 1 | 34 |
3 103 44 | 3750 | 2625 | 13 | 1 | 43 |
3 103 45 | 5000 | 3500 | 13 | 1 | 53 |
Avaibles Modules Single cabinet (British standard) | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 46 | 1250 | 875 | 13 | 1 | 23.5 |
3 103 47 | 2500 | 1750 | 13 | 1 | 34 |
3 103 48 | 3750 | 2625 | 13 | 1 | 43 |
3 103 49 | 5000 | 3500 | 13 | 1 | 53 |
Avaibles Modules Single cabinet - without batteries | ||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets |
3 103 51 | 1250 | 875 | - | 1 |
3 103 53 | 2500 | 1750 | - | 1 |
3 103 55 | 3750 | 2625 | - | 1 |
3 103 57 | 5000 | 3500 | - | 1 |
Avaibles Modules Double cabinet - without batteries | ||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets |
3 103 60 + 3 108 59 | 5000 | 3500 | - | 2 |
3 103 63 + 3 108 59 | 6250 | 4375 | - | 2 |
3 103 66 + 3 108 59 | 7500 | 5250 | - | 2 |
3 103 69 + 3 108 59 | 8750 | 6125 | - | 2 |
3 103 72 + 3 108 59 | 10000 | 7000 | - | 2 |
LEGRAND MEGALINE Brochure (1584.7 kB)
LEGRAND MEGALINE 1250 Datasheet (208.3 kB)
LEGRAND MEGALINE 2500 Datasheet (208.2 kB)
LEGRAND MEGALINE 3750 Datasheet (207.7 kB)
LEGRAND MEGALINE 5000 Datasheet (207.2 kB)
LEGRAND MEGALINE 5000/2 Datasheet (195.3 kB)
LEGRAND MEGALINE 6250/2 Datasheet (190.1 kB)
LEGRAND MEGALINE 7500/2 Datasheet (190.4 kB)
LEGRAND MEGALINE 8750/2 Datasheet (190.5 kB)
LEGRAND MEGALINE 10000/2 Datasheet (190.0 kB)
![](images/Layout/Weitere-Informationen_weiss.png)