LEGRAND DAKER DK Plus
Single-phase conventional UPS systems from 1 to 10 kVA
- Single-phase conventional UPS systems
- Power from 1 to 10 kVA
- Power factor 0,9 for 1000-3000, 1 for 5000-10000
- VFI-111 on-line double conversion
- User-friendly display
- Matching battery compartment to increase the uptime
- Smart battery management
- Optional automatic and manual bypass
- The battery can easily be replaced by the user
Daker DK UPS Plus is a single phase uninterruptible power supply with high frequency PWM technology, Double Conversion OnLine.
It delivers a rated power of 1000-2000-3000-5000-6000-10000VA, equipped with valve-regulated, hermetically-sealed accumulator batteries, contained in a specific compartment inside the UPS or in one or more external cabinets.
With the reversible screen, the Daker DK Plus UPS can be used in both tower and 19" rack configuration.
Functions
- View of the status, system parameters, charging status of the battery and faults.
- Built-in communication software to control the UPS and stop it in the event of a fault and to perform remote diagnostics of the main functions.
- Communication through SNMP/internet/network adaptor.
- Optional slot for network configuration.
- WEB/SNMP boards and relay interface that can provide isolated contacts for applications on industrial control panels or remote alarm panels.
- Automatic and manual bypass (optional) to ensure constant power supply for critical loads in the event of an electronic fault, overload or overheating or scheduled maintenance.
- Maintenance bypass switch (MTBS).
Characteristics
General characteristics Convertible UPS with batteries | 3 101 70 | 3 101 71 | 3 101 72 | 3 101 73 | 3 101 74 | |
Nominal power (VA) | 1000 | 2000 | 3000 | 5000 | 6000 | |
Active power (W) | 900 | 1800 | 2700 | 5000 | 6000 | |
Technology | On-line double conversion VFI-SS-111 | |||||
Waveform | Sinusoidal | |||||
Architecture | Convertible tower and 19" rack | |||||
Input characteristics | ||||||
Input voltage | 230 V | |||||
Input frequency | 50-60 Hz ± 5% autosensing | |||||
Input voltage range | 176V - 280V at full load | |||||
THD of input current | < 3% | |||||
Input power factor | > 0,99 | |||||
Output characteristics | ||||||
Output voltage | 230 V ± 1% | |||||
Output frequency (nominal) | 50/60 Hz (configurable via LCD panel) +/- 0.1% | |||||
Efficiency | up to 90% | up to 91% | up to 92% | up to 94% | ||
Peak factor | 1:3 | |||||
THD of output voltage | < 3% with linear load | |||||
Output voltage tolerance | ± 1% | |||||
Internal automatic bypass | included | |||||
External maintenance bypass | optional | |||||
Batteries | ||||||
Backup time extension | Yes | |||||
Backup time (min) | 9 | 10 | 7 | 6 | 5 | |
Communication and management | ||||||
Screen and signalling | Four buttons and five LEDs for real-time control of the status and the main parameters of the UPS | |||||
Communication ports | RS232 and USB serial ports | |||||
Remote control | Available | |||||
Connector for network interface | SNMP | |||||
Back feed protection | yes | |||||
Emergency power off (EPO) | yes | |||||
Mechanical characteristics | ||||||
Dimensions W x H x D (mm) | 440 x 88 (2U) x 405 | 440 x 88 (4U)x 600 | 440 x 196(4U) x 680 | |||
Net weight (kg) | 16 | 29,5 | 30 | 60 | 60 | |
Dimensions of battery cabinet H x W x D (mm) | 440 x196(4U)x425 | 440 x 88 (2U) x 600 | 440 x 88 (2U) x 680 | |||
Ambient conditions | ||||||
Ambient operating temperature (°C) | 0 to 40°C | |||||
Protection index | IP 21 | |||||
Relative humidity (%) | 20 to 80% | |||||
Noise at 1 m (dBA) | < 50 | |||||
Heat dissipation (BTU/h) | 490 | 654 | 818 | 892 | 1300 | |
Certifications | ||||||
Reference product standards | EN 62040-1, EN 62040-2, EN 62040-3 |
General characteristics Convertible UPS without batteries | 3 101 75 | 3 101 76 | 3 101 77 | 3 101 78 3-1 version |
Nominal power (VA) | 5000 | 6000 | 10000 | 10000 |
Active power (W) | 5000 | 6000 | 10000 | 9000 |
Technology | On-line double conversion VFI-SS-111 | |||
Waveform | Sinusoidal | |||
Architecture | Convertible tower and 19" rack | |||
Input characteristics | ||||
Input voltage | 230 V | 380V 3P+N | ||
Input frequency | 50-60 Hz ± 5% autosensing | |||
Input voltage range | 176V - 280V at full load | 305V - 485V | ||
THD of input current | < 3% | |||
Input power factor | > 0,99 | > 0,9 | ||
Output characteristics | ||||
Output voltage | 230 V ± 1% | |||
Output frequency (nominal) | 50/60 Hz (configurable via LCD panel) +/- 0.1% | |||
Efficiency | up to 94% | up to 90% | ||
Peak factor | 1:3 | |||
THD of output voltage | < 3% with linear load | |||
Output voltage tolerance | ± 1% | |||
Internal automatic bypass | included | |||
External maintenance bypass | optional | - | ||
Batteries | ||||
Backup time extension | Yes | |||
Backup time (min) | - | - | - | - |
Communication and management | ||||
Screen and signalling | Four buttons and five LEDs for real-time control of the status and the main parameters of the UPS | |||
Communication ports | RS232 and USB serial ports | RS232 serial ports | ||
Remote control | Available | |||
Connector for network interface | SNMP | |||
Back feed protection | yes | |||
Emergency power off (EPO) | yes | |||
Mechanical characteristics | ||||
Dimensions W x H x D (mm) | 440x88(2U)x680 | 440x132 (3U) x680 | ||
Net weight (kg) | 25* | 25 | 26 | 28 |
Dimensions of battery cabinet H x W x D (mm) | 440x88(2U)x680 | 440x132 (3U) x680 | ||
Ambient conditions | ||||
Ambient operating temperature (°C) | 0 to 40°C | |||
Protection index | IP 21 | |||
Relative humidity (%) | 20 to 80% | |||
Noise at 1 m (dBA) | < 50 | |||
Heat dissipation (BTU/h) | 892 | 1300 | 1636 | |
Certifications | ||||
Reference product standards | EN 62040-1, EN 62040-2, EN 62040-3 |
ORDERING INFORMATIONS
Avaibles Modules Convertible UPS with batteries | ||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Weight (kg) |
3 101 70 | 1000 | 900 | 9 | 16 |
3 101 71 | 2000 | 1800 | 10 | 29,5 |
3 101 72 | 3000 | 2700 | 7 | 30 |
3 101 73 | 5000 | 5000 | 6 | 60 |
3 101 74 | 6000 | 6000 | 5 | 60 |
Avaibles Modules Convertible UPS without batteries | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Weight (kg) | |
3 101 75 | 5000 | 5000 | - | 25 | |
3 101 76 | 6000 | 6000 | - | 25 | |
3 101 77 | 10000 | 10000 | - | 26 | |
3 101 78 3-1 version | 10000 | 9000 | - | 28 |
- LEGRAND DAKER DK Plus Brochure (862.2 kB)
- LEGRAND DAKER DK Plus 1000 Datasheet (155.0 kB)
- LEGRAND DAKER DK Plus 2000 Datasheet (154.8 kB)
- LEGRAND DAKER DK Plus 3000 Datasheet (154.3 kB)
- LEGRAND DAKER DK Plus 5000 Datasheet (209.8 kB)
- LEGRAND DAKER DK Plus 5000 - Inverter Datasheet (153.7 kB)
- LEGRAND DAKER DK Plus 6000 Datasheet (209.9 kB)
- LEGRAND DAKER DK Plus 6000 - Inverter Datasheet (153.8 kB)
- LEGRAND DAKER DK Plus 10000 - Inverter Datasheet (183.6 kB)