Produktgruppen > I/O Modules > MOXA ioLogik E2242

MOXA ioLogik E2242

Smart Ethernet remote I/O with Click&Go, 4 AIs, and 12 DIOs

MOXA ioLogik E2242
4251_12599.png
4251_8585.png
  • EigenschaftenEigenschaften
  • BeschreibungBeschreibung
  • Weitere InformationenWeitere Informationen
  • PDFPDF
  • Active communication with patented MX-AOPC UA Server and Active OPC server
  • Smart alarm management with email, SNMP traps, TCP, UDP
  • Save time and wiring costs with peer-to-peer communication
  • Front-end intelligence with patented Click&Go control logic, up to 24 rules
  • Simplify I/O management with MXIO library for Windows or Linux
  • Web browser configurations over HTTP
  • Supports SNMP v1/2c/3
  • Wide operating temperature range of -40 to 75°C (-40 to 167°F)
Die Moxa ioLogik E2242 wurde speziell auf Fernüberwachungs- und Alarmsysteme zugeschnitten. Dieses Active Ethernet I/O-Produkt bietet vier analoge Eingänge und zwölf konfigurierbare DIOs für ein 1:3-Verhältnis von analogen zu digitalen I/Os. Damit eignet sich diese Lösung perfekt für die Wassertank- und Umweltüberwachung, da hier ein analoger Eingang zum Auslösen von drei analogen Ausgängen für Alarmierung bei sehr hohen, hohen und geringen Werten verwendet wird. Mit der Moxa ioLogik E2242 können Sie Ihr Überwachungssystem einrichten, ohne dass Sie einen lokalen PC oder eine RTU benötigen.
ProdGrafik
Moxa’s ioLogik E2200 is a new type of Ethernet micro RTU controller, which is a PC-based data acquisition and control device that uses proactive, event-based reporting to control I/O devices. Unlike traditional RTUs, which are passive and must poll for data, Moxa’s ioLogik E2200 series with Active OPC Server makes seamless connection with SCADA systems a reality. In addition, SNMP is used for communicating with an NMS (Network Management System) for IT field users. The I/O status of an Ethernet micro RTU controller can be reported and controlled automatically on-site based on user specified conditions. This report-by-exception approach, which is new to PC-based monitoring, requires far less bandwidth than traditional polling methods.

Actice Alarming with Local Intelligence
The ioLogik E2200 Micro RTU supports simple and powerful Click&Go™ technology to deliver event-driven reports and allow alarm messages to be sent by email, TCP/UDP, and SMNP Trap with real-time stamps. With built-in Click&Go™ intelligence, the ioLogik E2200 micro RTU can be used for simple output control when it is triggered by input status, without the need for a PC controller. The ioLogik E2200 micro RTU reports I/O status automatically based on user-specified conditions. This report by-exception approach requires far less bandwidth than the traditional polling approach.


ioLogik E2242 Specifications


  • Inputs and Outputs

    Analog Inputs
    4 channels

    Configurable
    DI/Os 12 channels


  • Analog Input

    Type
    Differential input

    Resolution
    16 bits

    I/O Mode
    Voltage / Current

    Input Range
    ±150 mV, 0 to 150 mV, ±500 mV, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA

    Accuracy
    ±0.1% FSR @ 25°C
    ±0.3% FSR @ -10 and 60°C
    ±0.5% FSR @ -40 and 75°C

    Sampling Rate
    All channels: 32 samples/sec
    Per channel: 8 samples/sec
    Single channel: 100 samples/sec

    Input Impedance
    200k ohms (min.)

    Built-in Resistor for Current Input
    120 ohms


  • Digital Input

    Sensor Type
    Wet Contact (NPN or PNP) and Dry Contact

    I/O Mode
    DI or event counter

    Dry Contact
    • On: short to GND
    • Off: Open

    Wet Contact (DI to GND)
    • On: 0 to 3 VDC
    • Off: 10 to 30 VDC

    Common Type
    6 points per COM

    Isolation
    3k VDC or 2k Vrms

    Counter Frequency
    900 Hz

    Digital Filtering Time Interval
    Software selectable


  • Digital Output

    Type
    Sink

    I/O Mode
    DO or Pulse Output

    Pulse Output Frequency
    1 kHz

    Over-voltage Protection
    45 VDC

    Over-current Protection
    2.6 A (4 channels @ 650 mA)

    Over-temperature Shutdown
    175°C (min.)

    Current Rating
    200 mA per channel

    Isolation
    3k VDC or 2k Vrms


  • Power Requirements

    Power Consumption
    178 mA @ 24 VDC


  • MTBF (mean time between failures)

    Time
    204,391 hrs

    Database
    Telcordia (Bellcore)



    Common Specifications


  • LAN

    Ethernet
    1 10/100 Mbps RJ45 port

    Protection
    1.5 kV magnetic isolation

    Protocols
    Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP


  • Serial Communication

    Interface
    RS-485-2w: Data+, Data-, GND (3-contact terminal block)

    Serial Line Protection
    15 kV ESD for all signals


  • Serial Communication Parameters

    Parity
    None

    Data Bits
    8

    Stop Bits
    1

    Flow Control
    None

    Baudrate
    1200 to 115200 bps

    Protocol
    Modbus/RTU


  • Power Requirements

    Power Input
    24 VDC nominal, 12 to 36 VDC


  • Physical Characteristics

    Wiring
    I/O cable max. 14 AWG

    Dimensions
    115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)

    Weight
    under 250 g

    Mounting
    DIN rail or wall


  • Environmental Limits

    Operating Temperature
    Standard Models: -10 to 60°C (14 to 140°F)
    Wide Temp. Models: -40 to 75°C (-40 to 167°F)

    Storage Temperature
    -40 to 85°C (-40 to 185°F)

    Ambient Relative Humidity
    5 to 95% (non-condensing)

    Altitude
    Up to 2000 m

    Note Please contact us if you require products guaranteed to function properly at higher altitudes.


  • Standards and Certifications

    Safety
    UL 508

    EMI
    EN 61000-3-2; EN 61000-3-3; EN 61000-6-4;

    FCC
    Part 15, Subpart B, Class A

    EMS
    EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
    EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61000-6-2

    Shock
    IEC 60068-2-27

    Freefall
    IEC 60068-2-32

    Vibration
    IEC 60068-2-6

    Green Product
    RoHS, CRoHS, WEEE



  • Ordering Information

    Available Modules
    ioLogik E2242 Ethernet Micro RTU Controller with 4 analog inputs and 12 configurable DIOs,
    -10 to 60°C operating temperature
    ioLogik E2242-T Ethernet Micro RTU Controller with 4 analog inputs and 12 configurable DIOs,
    -40 to 75°C operating temperature





  • Kunden, die diesen Artikel gesehen haben, sahen auch
    Alle Cookies akzeptieren Ablehnen Konfigurieren

    Diese Website verwendet Cookies, um eine bestmögliche Erfahrung bieten zu können. Mehr erfahren.